Report Suspicious Activity
Overview
Quick Details
Place of Origin:
South Korea
Brand Name:
15/25/35kV LBS(oil type)
Type:
Other

 

EMT’s Oil type Load Break Switch with the ARC unit of the perfect extinction performance distribution level gang operated side-break switches for 15kV through 35kV on the overhead distribution feeders and outdoor distribution System.

 

The Oil Type LBS have been specially designed for these live-switching duties :

 

             ♦ Line Switching for Load Current (Parallel / Loop Switching), Load Transfer Switching.

             ♦ Transformer Magnetizing Current Switching-load currents.

             ♦ Cable Charging Current Switching.

 

EMT’s Oil Type LBS equipped Oil type High performance Arch Extinguishing Chamber and Switching Operation with Manual, or Motorizing .The Motorizing Type LBS can be operated remotely with EMT’s RTU by SCADA system DNP 3.0, or IEC 101 Protocol  

 

 

FEATURES

 

1) High Reliability

    Main circuit switching parts of the switch are in the steel-made hermetically-sealed enclosure which ensures the

   high rust-proof performance, therefore the switch can not be affected by the outdoor atmosphere.

    Moreover, the switch has long life and consequently it is free of maintenance.

2) Flexible Installation and Operation

    Operation   : Manual, or Motorizing Operation ( Available operation with SCADA system).

  * Automatic Trip & Closing as Reclosing Sequence : Optional

    Switching   ; Close (Close Handle ), Open (Open Handle) by Hook Stick

   Mounting   ; Horizontal Mounting on Pole mounted

 

In addition, the switch does not generate the regnition, re-strike and the abnormal voltage  in making and breaking current.

 

 

 

Unit

 

 

Technical   Data

Rated Voltage

 

kV

15

25

35

Maximum Rated Voltage

kV

15.2

25.8

36

Continuous Current

A

200/400/630

200/400/630

200/400/630

Rated Breaking Current

A

200/400/630

200/400/630

200/400/630

Short-Circuit Withstand Current

( 1sec,or 3sec )

kA

(Peak)

25/32.5

25/32.5

25/32.5

Power frequency withstand Dry/Wet

( 1 min )

kV

60/50

60/50

80/70

Impulse Withstand Voltage (BIL)

kV

125/150

125/150

170/200

Support Insulator

 

Porcelain / Polymer

Controller Operation

 

 

Manual / Motorizing

( Optional : Automatic Trip & Closing )

Standard

 

 

IEC 60265-1 / IEC60129 / ANSI 37.41

 

 

Company Information